Excellent Energy Efficiencyair Cooled Chiller

Product Description

Certification: ISO HS Code: 8418612090 Origin: China The EKAC series low-temperature high-efficiency total heat-recovery unit features leading-edge total heat recovery technologies and state-ofthe-art EVI enthalpy increase technologies. It can provide effective heating in temperatures as low as -20° C to provide "free" hot water of 45-60° C around the clock.
Compared with traditional air-cooled heat-pump unit + hot water equipment, units of this series can reduce operation cost by more than 60%. The unit combines energy efficiency, comfort, flexibility, reliability, and intelligence, and can be used to replace traditional centralized heating equipment to provide hot water without extra cost.
The unit helps saving energy and reducing green house gas emission, and brings substantial benefit to customers while protecting the environment.

Excellent Energy Efficiencyair Cooled Chiller
Excellent Energy Efficiencyair Cooled Chiller
Excellent Energy Efficiencyair Cooled Chiller
Model No.   EKAC210BRLHR EKAC42BRLHR EKAC360BRLHR EKAC840BRLHR EKAC1050BRLHR EKAC1260BRLHR
Air conditioning mode Nominal cooling capacity kw 63 126 189 252 315 378
Nominal heating capacity kw 63 126 189 252 315 378
Total power of nominal cooling capacity kw 19 38 57 76 95 114
Total power of nominal heating capacity kw 19 38 57 76 95 114
Water flow rate for nominal cooling capacity kw 19 38 57 76 95 114
Water flow rate for nominal heating capacity kw 19 38 57 76 95 114
Hot water mode Nominal water flow kw 68 136 204 272 340 408
Nominal heating capacity kw 68 136 204 272 340 408
Total power of nominal heating capacity kw 19.8 39.6 59.4 79.2 99 118.8
Cooling + heat recovery mode Nominal cooling capacity kw 63 126 189 252 315 378
Nominal heat recovery capacity kw 63 126 189 252 315 378
Total nominal power kw 19 38 57 76 95 114
Nominal water supply capacity at heat recovery side kw 19 38 57 76 95 114
Nominal water flow at
evaporator side
kw 19 38 57 76 95 114
Power supply v/ph/hz 380/3/50
Flow control   Electronic expansion valve
Refrigerant   R22
Heat  exchanger type Air conditioning side m³/h braze-welded panel-type heat exchanger
hot water side m³/h High-efficiency bucket heat exchanger
Compressor Qty Set 2 4 6 8 10 12
Fan Qty Set 2 4 6 8 10 12
Water
resistance
Air conditioning side kPa 45 45 45 45 45 45
hot water side kPa 65 65 65 70 70 70
Minimum
diameter for
water pipes
Air conditioning side inch ≥2 ≥2-1/2 ≥3 ≥4 ≥4 ≥5
hot water side inch ≥2-1/2 ≥3 ≥4 ≥4 ≥5 ≥5
Dimensions L×H mm  2012×1840
Width mm  880 2125 3370 4615 5860 7105
Power cable specification Section area of live line mm² ≥10 ≥35 ≥70 ≥95 ≥120 ≥150
Qty.of live lines   3
Section area of null line mm² ≥4
Qty.of live lines   1
Section area of grounding line mm² ≥10 ≥16 ≥35 ≥50 ≥60 ≥75
Qty.of grounding lines   1
Net weight kg 610 1220 1830 2440 3050 3660
Operation weight kg 630 1260 1890 2520 3150 3780
Note:
1. Air conditioning mode: Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172 m3/(h@kW);
outdoor ambient temperature 35°C. Test conditions for nominal heating capacity: outlet water temperature: 45°C; water flow: 0.172m3/(h@kW);
temperature of outdoor dry/wet bulb: 7°C/6°C.
2. Cooling + Heat recovery mode Test conditions for nominal cooling capacity: Hot water side: Outlet water temp. 45°C; nominal water flow for hot water mode.
Air conditioning side: Outlet water temp. 7°C; nominal water flow for heating mode.
3. Hot water mode: Test conditions for nominal water flow: temperature of outdoor dry/wet bulb: 20/15°C; Temperature of inlet/outlet water: 50/55°C.
4. Water resistance at the Air Conditioner side includes water pressure drop of the unit and the attached Y-shaped filter.
5. Water resistance at the hot water side includes water pressure drop of the unit and does not include the pressure drop at the Y-shaped filter and other components.
6. Pipes outside the unit need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK does not provide the pipes.
7. Full heat recovery units and other units can be combined to form partial heat recovery modular system. Full heat recovery units can also be combined to form a total heat recovery system. Modular units can be formed using the 1~16 basic modules. The above table lists the parameters for common module combinations.