Find Multifunction Water Source Heat Pump, Multifunction Air Source Heat Pump, Air Source Heat Pump on Industry Directory, Reliable Manufacturer/Supplier/Factory from China.

Inquiry Basket (0)
Home > Products > Multifunction Water (Air) Source Heat Pump > Multifunction Air Source Heat Pump (for Low Temperature area)

Multifunction Air Source Heat Pump (for Low Temperature area)

Basic Info

Model No.:  TT-27H1XFDMH

Product Description

Model NO.: TT-27H1XFDMH Work Environment: Low-temperature Heat Pump Application: Villa Family, Hotels, Factory Hospital, Student Apartments Cop: 4.0 Function: Cooling Air,Heating Air and Hot Water Transport Package: Exporting Plywood Package Origin: Guangzhou Heat Temperature: 50-70°C Heat Source: Air-source Certification: CE, ISO9001, CCC Ambinent: -25 Degree Area Trademark: tili Specification: CE HS Code: 841861900 Multifunction Air Source Heat Pump (for Low Temperature area)  is specially designed according to cold climate features. Its core philosophy is to solve the user's home eating during the cold climate in winter and spring, to make cooling in hot summer and autumn.

1) High efficiency in -25 degree area.
2) COP > 4.0
3) Air source
4) Copeland compressor
Multifunction Air Source Heat Pump (for Low Temperature area)
 

 
 
Main components:
1. Compressor: Copeland new designed Scroll Compressor with gas injection increase enthalpy can get a more high efficiency.

 
Multifunction Air Source Heat Pump (for Low Temperature area)
2. Heat exchanger: Stainless steel plate heat exchanger & Coaxial Coil heat exchanger.

 
3. Evaporator: Hydrophilic high efficiency fin-tube evaporator.
 
4. Expansion valves: Main thermal expansion valves & Spray thermal expansion valves. 
 
5. Electromagnetic valve: Emerson electromagnetic valve.

 
6. Fan:  FULIHUA fan with nylon fibred blades, durable, lower noise, longer life.                               
 
Strong points:
a. Hot water output temperature up to 65 degree.
b.  Suitable for cold area, safely working in -25 degree ambient temperature.
c. COP can be up to 2.4, at -15 degree.
d. Eco-friendly Refrigerant: R417A.
e. Automata tic defrosting function included (with reverse cycle valve inside).                                   
f. Anti-corrosion case: durable coating; no-screw design with stainless steel bolts and nuts, no rust.
g. General testing and operational test carried out for every before package in the factory.
h. Comprehensive protection, --- ensures trouble free operation in extremely cold ambient.
    1. Anti-freezing protection, 
    2.Water flow protection, 
    3.Over high pressure protection, 
    4.Over low pressure protection etc.Multifunction Air Source Heat Pump (for Low Temperature area)
Multifunction Air Source Heat Pump (for Low Temperature area)
Model   TT-27H4XCF TT-36H4XCF TT-46H4XCF TT-75H4XDF TT-92H4XDF TT-105H4XDF TT-150H4XDF TT-180H4XDF TT-270H4XDF
Power Supply V/ph/Hz 380/3/50
Max. Current  A 7.5 10 13 21 25 28.5 37 49 73.5
Cooling Capacity kw 7.5 10 12.5 20 25 27 37 50 75
Cooling Power Input kw 2.8 3.85 4.8 8.4 9.5 10.5 14 18.5 28.5
Heating Capacity kw 8 10.8 13.5 21.5 28 33.5 43 56.6 84.5
Heating Power Input kw 2.7 3.7 4.6 7.5 9.2 10.5 13.8 18 27
Water Heating Capacity kw 11.2 15.5 19.3 29.5 38.5 42 52 78 116
Water Heating Power Input kw 2.7 3.7 4.6 7.5 9.2 10.5 13.8 18 27
Refrigerant   R410A
Compressor   Scroll
Rated Wate Temp. ºC  55
Max. Water Temp. ºC  60
Operation Temp. Range ºC  -10 to 45
Cool Water Flow Rate m3/h 1.5 2.5 2.5 5 5 5 7.5 10 15
Hot Water Flow Rate m3/h 2 3 3 6 8 8 12 16 24
Water Connection   G1" G1" G1" G1" G1-1/4" G1-1/4" G2" G2" G2-1/2"
Noise  dB(A) ≤ 56 ≤ 58 ≤ 58 ≤ 60 ≤60 ≤60 ≤ 62 ≤64 ≤65
N.W./G.W. kg 125/175 150/200 250/300 280/330 305/355 580/630 662/712 950/1000
Product Size mm 755x545x1490 900x595x1490 900x690x1490 1200x920x1225 1425x1200x1690 2150x1420x1910 2460x1480x2200 2460x1680x2470
Packing Size mm 780x570x1620 925x620x1620 925x715x1620 1225x945x1355 1450x1225x1820 2175x1445x2040 2485x1505x2330 2485x1705x2600
Test Condition   cooling: ambient temp. (DB/WB): 35 ºC /24 ºC ; water temp.(In/Out): 12 ºC /7 ºC ;
heating: ambient temp. (DB/WB): 7 ºC /6 ºC ; water temp.(In/Out): 40 ºC /45 ºC ;
water heating: ambient temp. (DB/WB): 20 ºC /15 ºC ; hot water temp.(Initial/Final): 15 ºC /55 ºC      

Contact us if you need more details on Heat Pump. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Air Source Heat Pump、Multifunction Air Source Heat Pump. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Multifunction Water (Air) Source Heat Pump