Model No.: EKRV050A1/AR1
Product Description
Model NO.: EKRV050A1/AR1 Cooling Method: Air-cooled Selected Voltage: 380V/50HZ Trademark: Tili HS Code: 8418612090 Type: Air-Cooled Unit Structure: Integral Certification: CSA, RoHS, ISO, CE, CCC Origin: China Tili continuously improves and renovates multi-connection technologies, and applies various advanced technologies to EKRV series products. EKRV features large capacity, high efficiency, stable performance, wide operation range, no power supply contamination, and powerful intelligent control. In addition, EKRV
Features a full range of models for indoor and outdoor units and easy system design and installation, maximizing the satisfaction of customer requirements.
Ide Capacity Regulation Range and Precise Ambient Temperature Control:
By using a PWM valve to control the time ratio of unloading and loading status, the digital Scroll Compressor can continuously regulate the capacity within a range of 10%100%, increasing the precision of capacity regulation and the stability of indoor temperature, and providing differentiated air conditioning experience to customers.
Rapid Start Technologies:
EKRV series digital multi-connected central air conditioners can run in full load within a short period, quickly meeting indoor requirements.
The unit can safely run under light load for a long time. Even if the unit runs under light load for a long time, lubricant circulation is still smooth without requiring forcible oil return and causing unnecessary energy loss.
No Electromagnetic Interference:
Without a transducer, EKRV series digital multi-connected central air-conditioning units do not generate high-order harmonic and electromagnetic radiation, providing customers with healthy living and working environment. Therefore, these units can be widely used in places having strict requirements for electromagnetic compatibility (EMC), such as aerospace, hospital, and laboratory. Electromagnetic radiation causes harmonic pollution to the power supply and adjacent electric devices, affecting the performance of devices and even damaging devices. In addition, electromagnetic radiation causes interference to adjacent radio and electronic devices, resulting in misoperations and burn of devices.
Contact us if you need more details on Air Cooled Water Chiller. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Digital Scroll Chiller、Vrf Water Chiller. If these products fail to match your need, please contact us and we would like to provide relevant information.
Features a full range of models for indoor and outdoor units and easy system design and installation, maximizing the satisfaction of customer requirements.
Ide Capacity Regulation Range and Precise Ambient Temperature Control:
By using a PWM valve to control the time ratio of unloading and loading status, the digital Scroll Compressor can continuously regulate the capacity within a range of 10%100%, increasing the precision of capacity regulation and the stability of indoor temperature, and providing differentiated air conditioning experience to customers.
Rapid Start Technologies:
EKRV series digital multi-connected central air conditioners can run in full load within a short period, quickly meeting indoor requirements.
The unit can safely run under light load for a long time. Even if the unit runs under light load for a long time, lubricant circulation is still smooth without requiring forcible oil return and causing unnecessary energy loss.
No Electromagnetic Interference:
Without a transducer, EKRV series digital multi-connected central air-conditioning units do not generate high-order harmonic and electromagnetic radiation, providing customers with healthy living and working environment. Therefore, these units can be widely used in places having strict requirements for electromagnetic compatibility (EMC), such as aerospace, hospital, and laboratory. Electromagnetic radiation causes harmonic pollution to the power supply and adjacent electric devices, affecting the performance of devices and even damaging devices. In addition, electromagnetic radiation causes interference to adjacent radio and electronic devices, resulting in misoperations and burn of devices.
Model | EKRV040A1/AR1 | EKRV050A1/AR1 | EKRV060A1/AR1 | EKRV050A1/AR1 | EKRV060A1/AR1 | EKRV070A1/AR1 | EKRV080A1/AR1 | EKRV100A1/AR1 | EKRV120A1/AR1 | EKRV140A1/AR1 | ||
Nominal Cooling Capacity | kw | 10 | 12.5 | 15 | 12.5 | 15 | 19 | 25 | 28 | 33.5 | 40 | |
Nominal Heating Capacity | kw | 11.5 | 14 | 17 | 15 | 17.5 | 21 | 28 | 31.5 | 37 | 44 | |
Input power | Cooling | kw | 3.3 | 4.1 | 4.9 | 4.1 | 4.6 | 5.9 | 7 | 7.8 | 9.5 | 11.1 |
Heating | kw | 3 | 3.8 | 4.2 | 3.8 | 4.2 | 5.8 | 6.7 | 7.6 | 9.2 | 10.8 | |
Power supply | v/ph/hz | 220/1/50 | 380/3/50 | |||||||||
Rated current | Cooling | A | 15 | 18.6 | 22.3 | 7.9 | 8.7 | 12.2 | 14.8 | 16.4 | 18.3 | 21.4 |
Heating | A | 13.6 | 17.3 | 19.1 | 7.2 | 8.3 | 12 | 13.6 | 15.1 | 17.4 | 20.9 | |
Connector size | Liquid pipe | mm | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 12.7 | 12.7 |
Gas pipe | mm | 15.88 | 15.88 | 15.88 | 15.88 | 15.88 | 15.88 | 22.2 | 22.2 | 22.2 | 28.6 | |
Unit weight | kg | 120 | 125 | 129 | 125 | 129 | 135 | 290 | 300 | 305 | 350 | |
Noise | dB(A) | 59 | 59 | 60 | 59 | 60 | 61 | 56 | 57 | 60 | 60 | |
Refrigerant type | R410A | |||||||||||
Dimensions (W x D x H) | mm | 970x355x1050 | 970x355x1255 | 970x355x1050 | 970x355x1255 | 990x840x1840 | 1290x840x1840 | |||||
Model | EKRV160A1/AR1 | EKRV180A1/AR1 | EKRV200A1/AR1 | EKRV220A1/AR1 | EKRV240A1/AR1 | EKRV260A1/AR1 | EKRV280A1/AR1 | EKRV300A1/AR1 | EKRV320A1/AR1 | EKRV340A1/AR1 | ||
Nominal Cooling Capacity | kw | 45 | 50.5 | 56 | 61.5 | 68 | 73 | 78.5 | 85 | 90 | 95.5 | |
Nominal Heating Capacity | kw | 49.5 | 56 | 61 | 68 | 73 | 81 | 86.5 | 93.5 | 99 | 105.5 | |
Input power | Cooling | kw | 12.9 | 14.6 | 15.5 | 17.3 | 19.2 | 20.7 | 22.4 | 24 | 25.8 | 27.5 |
Heating | kw | 12.5 | 14 | 14.6 | 16.6 | 18.1 | 20.1 | 21.7 | 23.3 | 25 | 26.5 | |
Power supply | v/ph/hz | 380/3/50 | ||||||||||
Rated current | Cooling | A | 24.1 | 28.7 | 31.3 | 34.9 | 37.3 | 39.7 | 42.4 | 46.8 | 50.3 | 52.8 |
Heating | A | 23.8 | 27.7 | 30.8 | 33.2 | 35.1 | 38.3 | 42.2 | 45.3 | 49 | 52.5 | |
Connector size | Liquid pipe | mm | 12.7 | 12.7 | 15.88 | 15.88 | 15.88 | 15.88 | 15.88 | 15.88 | 19.05 | 19.05 |
Gas pipe | mm | 28.6 | 28.6 | 28.6 | 28.6 | 28.6 | 34.9 | 34.9 | 34.9 | 34.9 | 34.9 | |
Equalizer pipe size | mm | -- | -- | -- | -- | -- | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | |
Unit weight | kg | 360 | 370 | 590 | 590 | 600 | 655 | 665 | 710 | 720 | 730 | |
Noise | dB(A) | 60 | 61 | 61 | 62 | 62 | 62 | 62 | 62 | 63 | 63 | |
Refrigerant type | R410A | |||||||||||
Dimensions (W x D x H) | mm | 1290x840x1840 | 1990x840x1840 | 2280x840x1840 | 2580x840x1840 | |||||||
Model | EKRV360A1/AR1 | EKRV380A1/AR1 | EKRV400A1/AR1 | EKRV420A1/AR1 | EKRV440A1/AR1 | EKRV460A1/AR1 | EKRV480A1/AR1 | EKRV500A1/AR1 | ||||
Nominal Cooling Capacity | kw | 101 | 108 | 113 | 118.5 | 124 | 129.5 | 136 | 141 | |||
Nominal Heating Capacity | kw | 112 | 117 | 122.5 | 129 | 134 | 141 | 146 | 152 | |||
Input power | Cooling | kw | 29.2 | 30.3 | 32.1 | 32.7 | 34.7 | 36.5 | 38.4 | 40.2 | ||
Heating | kw | 28 | 28.9 | 30.6 | 32.1 | 32.7 | 34.7 | 36.2 | 38.1 | |||
Power supply | v/ph/hz | 380/3/50 | ||||||||||
Rated current | Cooling | A | 57.4 | 58.7 | 61.5 | 66 | 68.6 | 72.2 | 74.7 | 78.2 | ||
Heating | A | 55.4 | 56 | 59.9 | 62.8 | 65.9 | 68.3 | 70.2 | 73.9 | |||
Connector size | Liquid pipe | mm | 19.05 | 19.05 | 19.05 | 19.05 | 19.05 | 19.05 | 19.05 | 19.05 | ||
Gas pipe | mm | 34.9 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | 41.3 | |||
Equalizer pipe size | mm | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | 9.52 | |||
Unit weight | kg | 740 | 950 | 960 | 970 | 1190 | 1190 | 1200 | 1200 | |||
Noise | dB(A) | 63 | 64 | 64 | 64 | 65 | 65 | 65 | 65 | |||
Refrigerant type | R410A | |||||||||||
Dimensions (W x D x H) | mm | 2580x840x1840 | 3280x840x1840 | 3980x840x1840 | ||||||||
Notes: 1. The preceding cooling capacity is measured when the indoor dry/wet bulb reads 27°C/19°C, and the outdoor dry/wet bulb reads 35°C/24°C. 2. The preceding heating capacity is measured when the indoor dry/wet bulb reads 20°C/15°C, and the outdoor dry/wet bulb reads 7°C/6°C. 3. In the preceding table, heating capacity* is only applicable to heat pump units, and is omitted for cooling-only units. 4. For details about on-site power distribution and wiring for unit installation, see the nameplate or installation manual of the unit. 5. The noise levels are measured in a semi-silent room by averaging the noise levels at four sides of the unit. The checkpoints are 1 meter away from the unit at a height of (unit height + 1 meter)/2. In actual environment, the operation noise of the unit is generally higher due to ambient noise. |
Product Categories : Heat Pump Air Conditioner
Premium Related Products
Other Products
Hot Products
Horizontal Concealed Fan Coil UnitScrew Type Air Cooled Chiller (heat pump)Evi Air Source Heat Pump in Cold RegionsSwimming Pool Heat Pump for Heating and CoolingMultifunction Air Source Heat Pump (for Low Temperature area)Water Heat Pump Heating and CoolingNew product! R410a R134a rotary dehumidifier compressorDC Solar power 48v/60v mobile refrigeration freezer air cooling system KITSAUTO aircon compressor for EV RV traveling truck caravan grab excavator cabHVAC dc 12/12v R134a Cab of truck mining machine crane grab excavator camping car air conditioning system parts12/24vdc compressor for Mobile refrigerator motive freezer car fridgessupermarket display freezers cold storage of HVAC Refrigeration & Heat Exchange Equipment compressorHVAC R404A gas Refrigeration equipment Condensing Units for blood freezers cooling van supermarkets cateringCommercial cube ice making machine for beverage or drink cheap refrigeration unit Freezer for Ice Cream Ice cream compressortruck roof air conditioner accessories lanhai rv compressors for motorhome air conditioned compressor casement air conditionerHVAC solar power R134A DC 12v/24v/72v Speed variable compressor for EV RV truck sleeper cab tractor forklift